On May 30, 2012, ABB and Swiss data-center provider Green unveiled a 1 MW, 380 V direct-current (DC) distribution system at Green’s Zurich-West facility. The project demonstrated how a data center could reduce electrical conversion losses by distributing high-voltage DC to compatible servers and storage—but its reported savings were partner claims, not universal guarantees.
What ABB and Green actually unveiled
The installation was an internal DC power-distribution system, not a facility connected directly to a DC utility grid. Green’s Zurich-West data center still received alternating current (AC) from the electrical grid. The innovation was converting that power to DC within the facility and distributing it to compatible information-technology equipment.
As an Amazon Associate I earn from qualifying purchases.
The project served an approximately 1,100-square-meter expansion—about 11,800 square feet—with a rated distribution capacity of 1 MW and a distribution voltage of 380 V DC. The contemporary announcement described Zurich-West as Switzerland’s first Tier III-certified data center. That certification described the facility’s availability and maintainability characteristics; it did not mean that Tier III depended on the DC architecture.
Do these 3 things before closing this tab:
1Repair Windows errors before they cause bigger problems2Fix the driver behind crashes, sound loss and screen glitches3Clear out junk files and repair common Windows errorsAt the time, the project was described as the most powerful data-center application of DC. That was an attributed 2012 industry claim, not a current ranking.
#1 Best Overall
- 1️⃣【4-Digit Display & Power Calculation】: The Jesverty SPS series features a big bright 4-digit LED display that shows measured values of V/A/W that the unit outputs in real-time. The display resolution is up to 0.01V, 0.001A, and 0.1W.
- 2️⃣【Auto C.V. and C.C. Mode】: The Jesverty SPS series can be used as a constant-voltage*(C.V.) power supply and constant-current*(C.C.) power supply even when the load is changed. It switches automatically between CV mode and CC mode according to the changes in the load.
- 🌟Note: The V and A settings you set are the crossover point at which the mode switches.
- 3️⃣【Compact Body & Lightweight】: The Jesverty SPS series measured only 7.1(D)x3.35(W)x6.1(H)inches and weight of approx. 2.5lbs. It saves space on your workbench and can be moved around without any frustration.
- 4️⃣【Reliability and Safety】: The Jesverty SPS series is built with high-quality materials and reliable circuit designs that include multiple protection functions, such as short-circuit protection, over-load protection, grounding terminal, temperature-regulated fan, etc. to ensure performance and extend the lifespan.
Contemporary coverage of the announcement identified Green, ABB, and Validus DC Systems as the principal participants. Validus, a DC data-center specialist, supported the project after being acquired by ABB the previous year.
How the power path differed from conventional AC distribution
Servers ultimately use DC internally, but conventional data centers generally deliver AC to each server’s power supply, which converts it to the lower-voltage DC required by the electronics. A typical simplified path looks like this:
Conventional path:
Utility AC → UPS conversion → AC distribution → server power supply → DC electronics
DC-distribution path:
Utility AC → rectifier/UPS → DC distribution → DC-compatible server electronics
The DC design did not eliminate conversion altogether. The grid supplied AC, so an AC-to-DC conversion stage remained necessary. Its purpose was to reduce the number of conversions and move the remaining conversion closer to the facility’s power-entry and backup-power systems.
What’s actually slowing this PC down?
Pick the symptom - the matching free tool is one click away.
Every conversion produces some loss, usually as heat. Reducing conversion stages can therefore lower electrical losses and, in some circumstances, reduce the heat that the cooling system must remove. The resulting facility-wide benefit depends on the efficiency of every component, the load profile, distribution distances, and the cooling design—not simply on whether the system is labeled AC or DC.
Rank #2
- High-precision Encoder Knob: Different from general knobs, this DC power supply has a precise encoder knob. You can press the knob to switch each digit, and then turn the knob to customize each digit in the range of 0-9. Set the voltage or current you want more accurately.
- Output Enable/Disable Button: In the process of using the bench power supply, Output button can prevent us from forgetting to turn off the output and causing damage to the load. Just press this button to turn on or turn off the output of the power supply. This makes it more convenient for you to use the variable power supply.
- Overcurrent Protection: When the OCP function is turned on, if the load equipment is short-circuited during operation, the adjustable power supply will automatically stop output and send a buzzer to alert the user. Protect the adjustable power supply and load from damage.
- Precise 4-digit LED Display: The dc power supply is equipped with a high-definition 4-digit display with data accurate to 0.01 V and 0.001 A. It has constant voltage (C.V.) and constant current (C.C.) modes, which can be switched automatically. You can see the working status indicator on the display. Additionally, you can adjust the brightness of the screen according to your needs.
- USB Fast Charging Port: The variable power supply is configured with an 18W fast charging port. No more mplaining about mobile phones or repaired devices not being charged in time. The NANKADF dc power supply allows you to avoid this dilemma. It charges your devices quickly anytime, anywhere.
The project’s reported results
| Metric | Reported figure | What it means |
|---|---|---|
| DC distribution capacity | 1 MW | Project specification |
| Distribution voltage | 380 V DC | Project specification |
| Expansion area | About 1,100 m2 / 11,800 sq. ft. | Approximate project size |
| Efficiency improvement | 10% | Green and ABB’s reported comparison with comparable AC technology |
| Cost reduction | 15% | Partner-reported figure; the cost boundary was not specified |
| Potential grid-to-chip and cooling savings | Up to 20% | Green’s projection when the system was fully loaded |
These figures should be read carefully. The available report does not disclose the test duration, measurement equipment, load level, cooling boundary, AC baseline, or whether an independent organization verified the results.
The 10% figure was presented as a test result by Green and ABB. The 15% figure was described as a cost advantage, but the announcement does not establish whether it referred to capital expenditure, operating expenditure, electrical infrastructure alone, or total cost of ownership. Green’s 20% figure was a maximum projection tied to full loading; it was not a statement that the facility consistently saved 20%.
Why ABB, Green, and HP pursued the design
Green framed the installation as part of a long-term energy-optimization strategy. The expected benefits included lower conversion losses, reduced operating costs, a smaller electrical footprint, simpler maintenance in some areas, and potential reliability improvements.
ABB engineered the DC distribution system to Green’s requirements. HP supplied equipment designed or adapted for high-voltage DC operation, including the HP X1800 G2 Network Storage System, HP DL385 servers, and HP BladeSystem c3000.
Rank #3
- Precise 4-digit LED Display, Auto Power Calculation: The NICE-POWER DC power supply variable is a professional switching power supply regulation device with a high resolution of 0.01V and 0.001A. The variable power supply features a big bright 4-digit LED display that shows the adjustable power supply output values of Voltage (V) / Current (A) / Power (W) in real-time. The high-definition backlit 4-digit LED display provides an accurate and clear readout for the voltage, current and power values even if you are in low-light condition
- OUTPUT Switch Control: Sometimes we need to switch between different voltage or current outputs in experiments or work, but we often forget to turn off the output and causing damage to the load. The adjustable DC power supply OUTPUT key is designed to solve this problem, just with a single press of the added OUTPUT key, you can easily turn the output on or off. The required voltage and current can be adjusted without actual output power, which makes this benchtop DC power supply more secure and more energy saving. Also, you don't need to remove the load or turn off the power each time, making the variable DC power supply more convenient and efficient to use
- Reliability and Safety: Safety is our priority, all lab power supplies are certified. The adjustable switching regulated power supply is built with premium electronic components and reliable circuit designs that include multiple protection functions, such as leakage, grounding terminal, over-voltage, over-current, over-power, over-load, over-temperature, short-circuit protection to ensure stable working performance and prolong the life of the adjustable DC power supply effectively. KINDLY REMIND - For safety considerations, the DC power supply comes with only 110V input which meets the US standard voltage. 220V input is NOT available for this bench power supply
- 5V 2A USB Port, Intelligent Cooling Fan: Complaining about mobile phones or repaired devices not being charged in time? The NICE-POWER adjustable DC power supply allows you to avoid this dilemma. The variable power supply has built-in 5V 2A USB charging interface which can quickly charge any USB devices anytime. The adjustable power supply features with intelligent temperature-controlled fan and heat sink for excellent heat dissipation when the working temperature of the switching power supply exceeds 122℉/50℃, greatly reduce working noise and improving the DC regulated power supplies working efficiency and lifespan
- Compact Design, Lightweight and Portable: The DC voltage stabilized power supplies adopt stable vertical design with the shock-absorbing rubber feet on the bottom of bench supply, making it safer and more stable when using. The size of adjustable DC power supply is 8.4*3.3*5.5 inches and the lab power supply weighs only 2.6 lbs, which is very light and portable. You can carry your bench supply in and out of various workplaces
HP’s participation was important because a 380 V DC distribution bus cannot simply be connected to ordinary AC-only servers. The downstream equipment must have compatible power supplies, connectors, protection, and vendor support. HP presented the equipment as part of a broader high-voltage-DC strategy, but the project did not demonstrate that the entire server market had adopted that approach.
Reliability was an architectural question, not an automatic DC benefit
ABB said DC could enhance reliability while reducing footprint, installation, and maintenance costs. That claim depends on the complete electrical design. Relevant factors include:
- Utility-feed arrangement and redundancy.
- UPS, rectifier, and battery topology.
- DC bus segmentation and distribution redundancy.
- Protection, selective coordination, and fault-clearing time.
- Grounding, bonding, monitoring, and controls.
- Server compatibility and dual-corded equipment.
- Maintenance procedures and spare-parts availability.
- Technician training and contractor competence.
Fewer conversion stages may remove failure points, but DC introduces its own engineering requirements. High-voltage DC arcs behave differently from AC arcs because DC has no natural current-zero crossing. Switchgear, breakers, connectors, grounding systems, arc-flash controls, lockout/tagout procedures, and maintenance practices must therefore be selected for the actual DC system.
Why the savings were not guaranteed for every facility
Low utilization
The largest projected saving was tied to full loading. At low utilization, fixed losses in rectifiers, UPS equipment, cooling systems, and distribution equipment can reduce the advantage. A comparison must use the operator’s real load curve rather than only the nameplate capacity.
Rank #4
- Newly upgraded 150W DC power supply with higher voltage and current: This DC power supply can be freely switched between 15V 10A and 30V 5A. When the current value is set to 10A, the voltage value cannot exceed 15V. If the voltage value is set to 30V, the current value cannot exceed 5A. [The device can only output 150 W, but don't worry, the device cannot be set to output current and voltage values exceeding 150 W.]
- Ultra small size, Ultra full functionality, Cool fan automatic start : This DC power supply is only 10*18.5*8CM in size and weighs less than 1KG. It is lightweight, portable, and compact in design. When you cannot fit a larger power supply, this DC power supply is the most cost-effective choice. The DC power supply cool fan automatic starts, allowing the DC power supply to quickly cool down and extend its service life
- 3-Digit display and Encoder button precise adjustment : The voltage value of the DC power supply is accurate to 0.1V, while the current is accurate to 0.01A. By using the latest encoder buttons, the desired current and voltage values can be accurately adjusted. Just "set" the voltage and current, not "adjust" them. You can press the voltage and current encoder knobs to select the number to be adjusted, and then rotate the knob to set the value between 0 and 9. Each number can be easily set through a precise encoder knob. Encoder switches have replaced potentiometer switches, making your work easier, more accurate, and more efficient
- Instructions for use: (Please note: That when the DC power supply is too hot, please stop using it and wait for it to cool down before use to prevent irreversible damage to the DC power supply.)
- Wide range of input AC voltage: The input AC voltage is 100V~240V of NICE-POWER DC power supply model is SPS-E3010, and the frequency is 50~60Hz±10%, which meets the use of more than 90% of the countries and regions in the world. No matter where you are, you can use this DC power supply safely without the use of a transformer, which is safer and more secure
Mixed AC and DC environments
Many facilities contain storage, networking, appliances, and future equipment that do not share one DC input standard. Supporting both AC-only and DC-compatible loads may require parallel distribution systems, increasing operational complexity and reducing some footprint or cost benefits.
Equipment refresh and lifecycle support
The economics depend on continued access to compatible servers, storage, power supplies, connectors, and replacement parts. A system that is attractive at commissioning can become harder to maintain if later equipment generations use different rack-power architectures or return to standard AC inputs.
Modern high-density loads
The Zurich-West project predates today’s widespread deployment of AI accelerators, high-density GPU racks, liquid cooling, and newer rack-level power designs. Its 2012 equipment list should not be treated as a current recommendation or assumed to map directly onto modern AI halls.
Cooling accounting
Lower electrical losses can reduce heat production, but cooling savings depend on the thermal design and operating conditions. Operators should ensure that electrical savings and cooling savings are measured across defined boundaries and are not double-counted.
Best Value
- Intelligent Charging and Safety Detection: Our DC power supply features intelligent charging mode. The real-time display of charging power (Ah) keeps you informed of the battery status. Worried about overcharging? Rest easy knowing our power supply stops charging when your battery is full. With built-in detection of incorrect connections, ensuring safe and reliable charging.
- Overcurrent Detection Alarm: Easily activated with the 'OCP' button. Detects short circuits and overcurrents, triggering an alarm and stopping output to protect connected devices.
- Compact and Various Application: This DC power supply is less than 2.3 lb and measures only 7.59 x 3.35 x 6.1 inches, applies for laboratory, school, repair, electrolyzation, electroplate, brush plating, lamp test, aging testing, battery charge, home DIY and other requirements. 18W USB port Quickly charge your devices with high-speed 18W output for efficient charging, no worry about running out of power.
- Reliable and Safety: many safety measures are adopt in Kungber lab DC power supply - Grounding wire, Leakage protection,Thermal protection, Voltage overload protection, Power overload protection and Short-circuit protection. Kungber power supply use premium electronic components, provide reliable working status and prolong the life of product effectively. When the working temperature is more than 122℉/50℃,the intelligent thermal protection will active the cooling fan to lower the temperature
- What You Get - 1 x Kungber Variable DC Power Supply, 1 set of Output Power Cords , 1x Input Power Cord, 1 x User Manual, and Technical Support from Kungber.
What operators should evaluate today
A modern DC or hybrid-power assessment should examine the whole system rather than rely on a headline percentage.
Electrical design
- Utility input and rectifier/UPS efficiency at actual loads.
- DC bus voltage, topology, redundancy, grounding, and bonding.
- Short-circuit behavior, protection settings, selective coordination, and arc-flash risk.
- Fault-clearing time, monitoring, alarms, and controls.
IT compatibility
- The proportion of servers, storage, networking, and accelerators that can accept the proposed DC input.
- Dual-cord and failover requirements.
- Vendor warranties, approved power supplies, and rack-level distribution compatibility.
- A migration plan for AC-only equipment.
Economics
- Capital cost of rectifiers, switchgear, busways, protection, cabling, and rack equipment.
- Cost and availability of compatible IT hardware.
- Installation labor, maintenance contracts, training, and spares.
- Energy prices, utilization, expected payback, and the cost of operating a mixed environment.
Facility operations and sustainability
- Technician qualifications and safe maintenance procedures.
- Expansion flexibility and contractor availability.
- Measured facility energy reduction, including cooling.
- Battery lifecycle, embodied impacts, renewable-energy integration, and whether the design reduces total energy use rather than only distribution losses.
Enterprise operators considering this architecture would normally begin with an engineered power assessment, then obtain proposals from qualified infrastructure suppliers or integrators. ABB, Schneider Electric, Eaton, and Vertiv all offer data-center power and distribution portfolios, but a vendor’s general data-center offering is not proof that a particular 380 V DC design is suitable.
- ABB data-center infrastructure
- Schneider Electric data-center solutions
- Eaton data-center power infrastructure
- Vertiv data-center infrastructure
- Uptime Institute resilience and certification resources
What the Zurich-West project proved—and what it did not
The project proved that a substantial data-center expansion could be designed around a 380 V DC distribution system and compatible enterprise IT equipment. It also showed why DC was attractive to operators seeking fewer conversion stages and a differentiated efficiency strategy.
Recommended Free Tools
It did not prove that DC is always more efficient, cheaper, safer, or more reliable than AC. The reported 10% efficiency and 15% cost figures were not accompanied in the available coverage by a detailed methodology. The 20% number was a qualified projection. Nor does the announcement establish the project’s long-term operating results, later expansion, or industry-wide adoption.
Its historical importance is therefore best understood as a serious real-world demonstration at a time when high-voltage DC was still an emerging data-center approach. For a 2026 facility, the relevant question is not whether the Zurich numbers can be copied. It is whether a complete DC or hybrid architecture delivers a verified lifecycle advantage for the facility’s present equipment, safety regime, load profile, and future expansion plans.
Conclusion
ABB and Green’s 2012 Zurich-West installation was a 1 MW, 380 V DC distribution project serving an approximately 1,100-square-meter expansion. By distributing DC to compatible HP servers and storage, the partners aimed to reduce conversion losses and associated cooling demand. Green and ABB reported a 10% efficiency improvement and 15% lower cost, while Green projected up to 20% grid-to-chip and cooling savings at full load.
Those results remain useful as historical evidence of what the architecture was intended to achieve, not as universal performance guarantees. For modern operators, compatibility, protection, safety, redundancy, lifecycle support, utilization, and independently measured whole-facility economics matter as much as nominal conversion efficiency.